A simple guide to how valve pressure ratings reduce as temperature increases, and why P-T tables must be checked for elevated-temperature service.
A valve pressure rating is not one fixed number for every temperature. Most ratings are quoted at a baseline temperature, often around room temperature. As the operating temperature increases, the allowable working pressure normally reduces because the valve material becomes weaker at higher temperatures.
Important: Do not select a valve using only the pressure class printed on the body. For hot water, steam, thermal oil, or high-temperature process service, always check the pressure-temperature rating for the exact material and standard.
Valve bodies, bonnets, bolting, seats, and seals all have temperature limits. At higher temperatures, metallic materials can lose strength and soft seat materials can also lose sealing performance. This means a valve that is acceptable at room temperature may not be suitable at the same pressure when the service is hot.
Basic example: A Class 150 carbon steel valve may be commonly associated with about 19.6 bar at low temperature. At 200°C, the allowable pressure is lower, so the full pressure-temperature table must be checked before quoting or installing.
| Term | Simple meaning | Why it matters |
|---|---|---|
| Class 150 / 300 | ASME / ANSI pressure class references. | The class gives a pressure-rating family, but the allowable pressure still changes with material and temperature. |
| PN rating | Metric pressure class reference, such as PN16 or PN40. | Useful for flange and valve selection, but it is still subject to temperature and material limits. |
| WCB | A common cast carbon steel valve body material. | Often used in general process, steam, oil and gas, and industrial service. |
| Allowable pressure | The maximum working pressure allowed at a stated temperature. | This is the value to check when the service is above room temperature. |
| Design temperature | The maximum temperature the system is designed to reach. | Use this temperature when checking the valve rating, not just the normal operating temperature. |
The table below gives indicative Class 150 carbon steel WCB values. I have filled the notes column with short practical comments instead of leaving blank cells, so the table is easier to read and looks more complete.
| Temperature | Allowable pressure | Practical note |
|---|---|---|
| -29°C to 38°C | 19.6 bar | Baseline low-temperature rating often quoted for Class 150. |
| 50°C | 19.2 bar | Small reduction; usually close to the baseline rating. |
| 100°C | 17.7 bar | Rating starts to reduce noticeably. |
| 150°C | 15.9 bar | Derating continues; check if system pressure is close to this value. |
| 200°C | 14.8 bar | Important for steam and hot process service. |
| 250°C | 13.8 bar | Confirm valve body, trim, gasket, and packing suitability. |
| 300°C | 12.8 bar | High-temperature service; check full B16.34 table. |
| 350°C | 11.7 bar | Significant derating; confirm against manufacturer data. |
| 400°C | 10.2 bar | Near upper practical range for many carbon steel applications. |
| 425°C | 9.3 bar | Close to practical limit for WCB; specialist review recommended. |
Class 300 has a higher pressure capability than Class 150, but it still derates as temperature increases. The higher class does not remove the need to check the pressure-temperature table.
| Temperature | Allowable pressure | Practical note |
|---|---|---|
| -29°C to 38°C | 51.1 bar | Baseline low-temperature rating for Class 300. |
| 100°C | 46.6 bar | Reduced from baseline; still substantially higher than Class 150. |
| 200°C | 38.6 bar | Important check point for steam and hot process service. |
| 300°C | 33.4 bar | Confirm against full B16.34 table and manufacturer data. |
| 400°C | 26.8 bar | Significant derating at elevated temperature. |
| 425°C | 24.3 bar | Near upper practical range; confirm for final design. |
Best table approach: For website or catalogue tables, avoid blank cells where possible. Use short entries such as “check datasheet”, “standard derating range”, “not usually specified”, or “confirm for final design”. This keeps the table tidy without pretending to provide extra certified data.
Steam service needs special attention because steam pressure and temperature are linked. The valve must be rated above the pressure required at the design temperature, and the valve materials, seats, gaskets, and packing must also be suitable for steam.
| Steam check | What to confirm |
|---|---|
| Saturation pressure | Check the steam saturation pressure at the design temperature. |
| Valve P-T rating | Confirm the allowable valve pressure at that same temperature. |
| Seat and packing | Make sure the soft goods are suitable for steam temperature. |
| End connections | Check flange class, thread type, gasket, bolting, and installation standard. |
Example: Steam at 200°C has a saturation pressure of approximately 15.5 bar. A valve must be rated above the required pressure at 200°C, not just at room temperature.
The values for carbon steel WCB are not automatically valid for stainless steel, duplex, bronze, cast iron, ductile iron, plastics, or special alloys. Each material and standard has its own limitations.
| Carbon steel Common for steam and process service, but must be checked at elevated temperature. |
Stainless steel Good corrosion resistance, but still has pressure-temperature limits. |
Bronze / iron Often used in water and general service; check face type, gasket and temperature suitability. |
| Plastic valves Pressure ratings can reduce quickly with temperature. |
Soft seats PTFE, EPDM, NBR, Viton and other seats have their own temperature limits. |
Certification Critical applications may require test certificates or compliance to a project specification. |